Filters
Close

Copeland Emerson SC Series Leak Sensor 448A

SKU: 809-1203

Download Wiring and Controller Setup

 

Compatible Copeland Emerson Multi-Zone Leak Detector Panel Part # 851-4550 only.

 

The SC refrigerant leak sensor is a series of transmitters for measuring concentration of different gases. The transmitter is available in the Standard Room Type. The sensor heads are semi-conductive, which provides a long lifetime and stability, but with limited selectivity.

The transmitter gives a non-linear output signal (4 to 20mA or 0 to 10V DC) proportional to the gas concentration.

Technical Data:

  • Refrigerant: 448a
  • Sensor Type: Semiconductor
  • Response Time (T90): < 10 seconds
  • Operating Temperature: -40°F to 122°F (-40°C to 50°C)
  • Operating Humidity: 10 to 90% Rh (non condensing)
  • Dimensions: 130x82x56 mm
  • Housing: Polycarbonate / ABS
  • Output Signal: 4 to 20mA (max 500 ohm) or 0 to 10V DC
  • Calibration: Zero/span ≥ once per year
  • Lifetime Sensor: > 5 years (replacement recommended every 5th year or when unit cannot be calibrated)
  • Power Supply: 12 to 30V DC (Recommended 24VDC @ 15W,120V, DIN Rail mount P/N 250-2541)
  • Cable Gland: 1 x M16
  • Part Number: 809-1203
Categories